NDB2Z-63 dedicated to the low voltage power distribution system of industrial, buildings, energy communications and infrastructure.
1P 2P
2、Model and implication:
3、Main technical specification
●Electrical parameters
○Rated working voltage and relevant breaking capacity:
Pole
1P
2P
certificate
Rating current(A)
1A, 1.2 A, 1.5 A, 1.6 A, 2A, 3A, 4A, 5A, 6A, 7A, 8A, 10A, 12A,13A, 15A, 16A, 20A, 25A,30A,32A, 40A, 50A, 60A, 63A
Item
Icu
Voltage
DC125V
10kA
/
CCC CE/TUV
DC220V/250V
10kA
/
DC250V
/
10kA
DC440V/500V
/
10kA
Voltage
DC125V
10kA, U1
/
UL1077
DC220V
4.5 kA, U1
/
DC250V
/
10kA, U1
DC440V
/
4.5 kA, U1
○Impulse withstand test voltages: 4kV ○electrical endurance: 1500 times;Mechanical endurance: 20000 times Product certification and implementation standard.: ○Product certificate:CCC,CE,TUV,UL1077; ○Product certification standard:GB/T 14048.2,IEC60947-2,UL1077; Environmental requirements:RoHS Isolation function ○Practical breaking instructions ○View window within the green identification said contact in the off position Tripping characteristic B type curve Protection of short circuit current small load rated current:1A~63A tripping characteristic:The instantaneous tripping range 6In(1±20%)
C type curve Protect normal load and distribution wire cable rated current:1A~63A tripping characteristic:The instantaneous tripping range 12In(1±20%) ●Wiring diagram:
1P 2P
4、Normal working environment
●Ambient temperature:-40℃~+70℃
●Air relative humidity:≤95%
●Altitude:≤2000m
●pollution degree: 3
●Service place without significant vibration and impact
Modular construction,can be installed in EN60715 TH 35mm x 7.5mm standard guide rail.
8、Connect line requirements
Standard cross-sections of round copper conductors: 1~35mm2
Terminal screw: M5 ,Rated torque : 2.0N.m
9、Packing storage
Quantity(1P product:12 PCS/box,2P product:6PCS/box),Packing boxes of products should be stored in the air circulation and relative humidity is not more than 80% and the temperature is not higher than + 70 ℃,Not less than – 40 ℃ in the air around without acid, alkali or other corrosive gases stored in the warehouse. In the above conditions, the storage period since the production date not more than three years.
10、Accessories list and mounting
●OF2 auxiliary contacts Installed on the left hand of the NDB2Z – 63 circuit breaker left, indication circuit breaker on-off state;
●SD2 indicator contacts Installed on the left hand of NDB2 Z – 63 circuit breaker , indication failure tripping status of breaker;
●MX+OF2 shunt trip release Installed on the left hand of NDB2 Z – 63 circuit breaker, remote control of the circuit breaker’s tripping;
11、 Notice
1、Customers who disassemble the product without approval shall undertake relevant quality problems by themselves;
2、 Do not touch the naked part of conductive components when the product is power on;
3、Don’t test characteristics of the breaker optionally, the manufacturer is irresponsible for such quality problems;
4、Keep wiring correct to prevent malfunction or damage of wiring terminals.
5、Please open the cover when installing the accessory. Please refer to OF2, SD2, MX+OF2 Instruction for details.
1. Applicable Scope and Purpose of Circuit Breaker The NDM2Z-400 DC molded case circuit breaker (hereinafter referred to as circuit breaker) applies to the DC system application environment and the electric circuit with the working volta...
1. Applicable Scope and Purpose of Circuit Breaker The NDM2L-250 molded case circuit breaker with the residual current protection (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with the AC 50/60H...
1、Application Scope and Purpose The NDB2LE-25 series of residual current action circuit breakers provide the ground leakage, direct or indirect electric shock by human body and othe...
1.Applicable Scope and Purpose of Circuit BreakerThe NDM2L-630 molded case circuit breaker with the residual current protection (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with the AC 50/60Hz, the worki...