1. Applicable Scope and Purpose of Circuit Breaker
The NDM2L-400 molded case circuit breaker with the residual current protection (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with the AC 50/60Hz, the working voltage of AC415V and the working current up to 400A. With the overload, short circuit and undervoltage protection functions, the circuit breaker can protect lines and power equipment from damage. Meanwhile, they can deal with the personal safety, fire hazards and other potential risks caused due to long-term ground faults that can’t be detected with the overcurrent protection function.
2.Specification and Model Description of CircuitBreaker
A: The N-pole isn’t installed with an overcurrent release, but always
B: The N-pole isn’t installed with an overcurrent release, but on-off
C: The N-pole is installed with an overcurrent tripper, and on-off with
16
Rated current
See Table 2
17
Cabling type
No code: Normal product
P: Connection busbar
Z1: Rear-plate connection
Z2H: Plug-in rear-plate connection
Z2Q: Plug-in front-plate connection
Z3H: Integrated plug-in rear-plate connection
Z3Q: Integrated plug-in front-plate connection
Note: 1.When the operation mode is electric operation or manual operation, the residual action current gear, residual current action time gear, and leakage indication button can’t be adjusted; 2.Lower inlet wire not allowed for the 4P Type A product.
3. Main Technical Parameters of Circuit Breaker
Table 2 Main Technical Parameters of Circuit Breaker
Rated residual short-circuit making and breaking capacity I△m(kA)
0.25 Icu
Rated residual action current I△n(mA)
Non-time delay
Type AC
Type V 30/300/500/1000
Type A
Type V 30/300/500/1000
delay
Type AC
Type V 300/500/1000
Type A
Type V 300/500/1000
Rated residual non-action current I△no(mA)
0.5I△n
Residu al current actiontime
Residual current
I△n
2I△n
5I△n
10I△n
Non-time delay
Maximum breaking time (s)
0.2
0.1
0.04
0.04
delay
Maximum breaking time (s)
0.5, 1.152.15
0.35, 12
0.25, 0.91.9
0.25, 0.91.9
Limit non-driving time (s)
/
0.1, 0.51
/
/
Operating performance (times)
Electrical life
7500
Mechanica l life
Maintainable free life
10000
Maintainable life
20000
3.1Selection of the circuit breaker connecting bus or cable cross-section area: Table 3 Selection of the NDM2L-400 Connecting Bus or Cable Cross-section Area
Rated current (A)
225
250
315, 350
400
Wire cross-section area (mm2)
95
120
185
240
3.2Tightening Torque of the Circuit Breaker Terminal and Mounting Screw Table 4 Tightening Torque of the Circuit Breaker Terminal and Mounting Screw
Model
Thread diameter (mm)
Torque (N·m)
NDM2L-400
M10
20
M6
6
3.3Derating factor of temperature change for the circuit breaker Table 5 Derating Factor Table of Temperature Change for the Circuit Breaker
Model
Derating factor of product temperature change
NDM2L-400
Temperat ure (℃)
40
45
50
55
60
65
70
Derating factor
1
0.981
0.962
0.942
0.922
0.901
0.879
Note: 1) When the operating ambient temperature is below ﹢40℃, the product can be used normally without derating capacity. 2) The above derating factors are measured at the frame current.
3.4High-altitude derating factor of the circuit breaker
Table 6 High-altitude Derating Factor Table of Circuit Breaker
Elevation (m)
Working current correction coefficient
Power frequency withstand voltage correction coefficient
Isolation voltage correction coefficient(V)
2000
1
3500
1000
2500
1
3500
1000
3000
0.98
3150
900
3500
0.97
3000
850
4000
0.95
2800
810
4500
0.94
2650
770
5000
0.93
2500
730
4.Normal Working Environment of Circuit Breaker 1)The altitude of the installation site doesn’t exceed 2,500m. See the “High-altitude Derating Factor Table of Circuit Breaker” for the derating factor at the altitude; 2)The ambient temperature is -35℃ ~ + 70℃; the average within 24 h shall not be more than +35℃. If the ambient temperature is higher than +40℃, the user needs to reduce the capacity. See the “Derating Factor Table of Temperature Change for the Circuit Breaker” for the derating factor; 3)Its relative humidity at an ambient temperature of +40℃ should not exceed 50%. A higher relative humidity is allowed at a lower temperature. For example, the relative humidity at 20℃ can reach 90%; for frost due to temperature change, the corresponding measures should be taken; 4)The product can withstand the effects of wet air, salt mist, oil mist and mould; 5)The installation category of the circuit breaker connected to the main loop is: Category Ⅲ (power distribution and control level), The installation category of the circuit breaker not connected to the main loop is: Category Ⅱ (load level); 6)The pollution level is Level 3; 7)The product should be installed in places that are free from explosive media, media corrosive to metal, insulation damaging gas, and conductive dust, which should be also avoided from snow and rain; 8)In case of stricter user conditions than the above description, negotiate with the manufacturer.
5.Outline and Mounting Hole Dimensions of Circuit Breaker 5.1Outline and mounting hole dimensions of circuit breaker
Note: The limit deviation not indicated with the tolerance dimensions is as per GB/T 1804-c.
5.2Safe mounting distance of circuit breaker Table 7 Insulation Distance Mounted in the Metal Cabinet (Unit: mm)
Mounting distance
A (inlet wire end to the cabinet face)
B (distance from side to the cabinet face)
C (outlet wire end to the cabinet face)
Model
With a terminal cover
Without a terminal cover
NDM2L-400
25
120
35
35
Table 8 Minimum Center Distance between Rowed Circuit Breakers (Unit: mm)
Model
Width of circuit breaker
I Center distance
3 poles
4 poles
3 poles
4 poles
NDM2L-400
150
198
190
238
Note: Check the connected busbar or cable during rowing or stacking of the circuit breaker to ensure that the air insulation distance won’t be reduced.
Table 9 Minimum Distance between Stacked Circuit Breakers (Unit: mm)
Model
H (distance of circuit breaker from bottom)
With a terminal cover
Without a terminal cover
NDM2L-400
155
155
Note: 1) Bare cable connection 2)Cable insulating connection 3)Connection without insulation
Requirements: Check whether the terminal cover or phase partition is assembled properly before products are energized.
1. Applicable Scope and Purpose of Circuit Breaker The NDM2Z-400 DC molded case circuit breaker (hereinafter referred to as circuit breaker) applies to the DC system application environment and the electric circuit with the working volta...
1. Applicable Scope and Purpose of Circuit Breaker The NDM2Z-63 DC molded case circuit breaker (hereinafter referred to as circuit breaker) applies to the DC system application environment and the electric circuit with the working voltage of DC250...
1. Applicable Scope and Purpose of Circuit Breaker The NDM2Z-125 DC molded case circuit breaker (hereinafter referred to as circuit breaker) applies to the DC system application environment and the electric circuit with the working voltage of DC25...
The NDB2LE-40 series of residual current action circuit breakers provide the ground leakage, direct or indirect electric shock by human body and other faults protection, wh...