The NDM5-1600 series of moulded case circuit breakers (referred to as circuit breakers) have a rated insulation voltage of 1000V and apply to circuits with the AC 50Hz/60Hz, the rated working voltageAC380/400/415V、AC500V、AC660/690V、AC800V,Vand rated working current (800A to 1250A). The circuit breakers are used for distributing power while protect the overload, short circuit and under-voltage (with a under-voltage release) of lines and power units as well as the infrequent starting, braking, overload and short circuit of motors. Each voltage level and short-circuit section capacity of the circuit breaker can be connected with the lower incoming line.(Except AC800V )
Normal Working Environment of Circuit Breaker 1) The altitude of the installation site doesn’t exceed 2,500m. See the “High-altitude DeratingFactor Table of Circuit Breaker” for the derating factor at the altitude; 2) The ambient temperature is -35℃ ~ + 70℃; the average within 24 h shall not be more than+35℃. If the ambient temperature is higher than +40℃, the user needs to reduce the capacity.See the “Derating Factor Table of Temperature Change for the Circuit Breaker” for the derating factor; 3) Its relative humidity at an ambient temperature of +40℃ should not exceed 50%. A higherrelative humidity is allowed at a lower temperature. For example, the relative humidity at20℃ can reach 90%; for frost due to temperature change, the corresponding measuresshould be taken; 4) The product can withstand the effects of wet air, salt mist, oil mist and mould; 5) The installation category of the circuit breaker connected to the main loop is: Category Ⅲ (power distribution and control level), The installation category of the circuit breaker notconnected to the main loop is: Category Ⅱ (load level); 6) The pollution level is Level 3; 7) Degree of protection: IP 20; 8) The product should be installed in places that are free from explosive media, media corrosiveto metal, insulation damaging gas, and conductive dust, which should be also avoided fromsnow and rain; 9) In case of stricter user conditions than the above description, negotiate with the manufacturer.
NDC1(Z)-40 AC Contactor, which used in 50Hz(60Hz) AC circuit with the rated voltage of 1000V. It is used in AC-3 type, with the rated working voltage of 415V and rated working current of 40A, to realize distant connection and disconnection of the ...
Gemeral SVM5H series of moulded case circuit breaker is supplied with rated insulating voltage 1150V and used for circuit of A.C. 50Hz, rated operating voltage AC 1140V. (or below), rated operating current up to 630A for infrequent changing over a...
1. Applicable Scope and Purpose of Circuit Breaker The NDM2(X)-125 molded case circuit breaker (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with the AC 50/60Hz, the working voltage of AC690V and workin...